Industrial Burners

Product Details

  • Mixer body: cast iron G25
  • Gas inlet body: cast iron G25
  • Flame tube: AISI304 / AISI310
  • Nozzle: AISI310
  • Fixing flange: iron
  • Pre-heated air: up to 450°C
  • Optional refractory block, max. temperature: 1,750°C
  • Capacity range: 30 to 300 kW
  • Air and gas pressure at burner: 45 mbar
  • Adequate to different types of gas: CH4/LPG/propane/etc.
  • Turn-down range: 4:1
  • Excellent flame stability: excess air excess fuel on ratio firing
  • Low NOx level

 

The main feature of RT burners is the dual air mixing. The primary air mixes on the combustion head; the secondary air, guaranteed by holes on the flame tube, completes the mixing making the flame longer. This extends the life of the radiant tube and increases the heat transfer efficiency. Calibration of RT burners is simplified by plugs for gas and air flow controls. Air-gas ratio usually used in radiant tube burners are 12:1, 13:1. RT burners may operate with cold air and preheated air up to 450°C (by using heat exchangers) allowing up to a 25-30% of energy saving.

Downloads

Support

Onsite Diagnostics

If you require onsite diagnostics or technical assistance with any of our products please give us a call

01905 797989

More Support

Duomo (UK) Ltd. offer detailed technical advice and support for our entire product range. Whether it's pre or post sales information you need we are here to help. If you can't find the information you need online then contact us direct.

Contact

Servicing

Service Request

We recommend Duomo Gas Detection products are serviced at least annually to ensure efficacy and extend sensor life. Our qualified team of engineers are available Nationwide.

All rights reserved © Duomo 2019.